Resumen:
Voltage collapse phenomena are highly affected by reactive power generation limits. Saturation of the reactive power generation limits of a unit may result in a deterioration of the voltage stability. However, in some cases when the power network is operating close to the voltage collapse point, the reactive power generation saturation of a unit can change the system voltages immediately from stable to unstable; thus, a dynamic voltage collapse leading to blackout may follow. This paper presents a steady-state analysis of the immediate instability caused by reactive power generation saturation phenomena. For this purpose, the paper proposes a novel index that evaluates when and why a reactive power generation saturation will only result in a deterioration of the system voltage stability or, on the contrary, it will make the system voltages immediately unstable.
Palabras Clave: Reactive power generation limits; Voltage stability; Voltage collapse; Transcritical bifurcation
Índice de impacto JCR y cuartil WoS: 1,259 (2009); 3,300 - Q2 (2023)
Referencia DOI: https://doi.org/10.1016/j.epsr.2009.03.006
Publicado en papel: Septiembre 2009.
Publicado on-line: Abril 2009.
Cita:
F.M. Echavarren, E. Lobato, L. Rouco, Steady-state analysis of the effect of reactive generation limits in voltage stability. Electric Power Systems Research. Vol. 79, nº. 9, pp. 1292 - 1299, Septiembre 2009. [Online: Abril 2009]